4. Understanding 4–20 mA Current Loops


0

A Practical Guide for Automation Technicians

One of the most important signals in industrial instrumentation is the 4–20 mA current loop.

If you work with pressure transmitters, level transmitters, flowmeters, temperature transmitters, pH transmitters, control valves, I/P transducers, or PLC analog input cards, you will see 4–20 mA signals many times.

For automation technicians, this is a signal that must be understood very well because it connects the field instrument to the PLC, controller, or control system.

In simple terms:

A 4–20 mA signal is an analog current signal used to represent a process value.

Example:

0 PSI   = 4 mA
50 PSI = 12 mA
100 PSI = 20 mA

The book Lessons In Industrial Instrumentation explains 4–20 mA analog current signals, how they relate to process variables, how 2-wire loop-powered transmitters work, and how technicians can troubleshoot current loops using milliammeters, clamp-on milliamp meters, test diodes, shunt resistors, and voltage measurements.


Why 4–20 mA Is So Common

The 4–20 mA signal is widely used because it is practical, reliable, and easy to troubleshoot.

A transmitter measures a real process condition and converts it into current.

Example:

Pressure Transmitter → 4–20 mA Signal → PLC Analog Input → Scaled PSI

This signal is used for many process variables:

Process VariableCommon Instrument
PressurePressure transmitter
LevelLevel transmitter
FlowFlow transmitter
TemperatureTemperature transmitter
pHpH transmitter
WeightWeight transmitter
Valve PositionPosition transmitter
Control OutputI/P transducer or valve positioner

The Basic 4–20 mA Relationship

A 4–20 mA signal represents a process range.

The most common interpretation is:

Current SignalPercent of Range
4 mA0%
8 mA25%
12 mA50%
16 mA75%
20 mA100%

Example:

A pressure transmitter is ranged from 0 to 100 PSI.

PressureCurrent
0 PSI4 mA
25 PSI8 mA
50 PSI12 mA
75 PSI16 mA
100 PSI20 mA

This means that if a technician measures 12 mA, the process should be around 50% of range.

For this example:

12 mA = 50 PSI

Important Concept: 4 mA Is Not Zero Current

This is one of the most important things to understand.

In a 4–20 mA signal:

4 mA = 0% process value
0 mA = bad signal condition

That means 4 mA does not mean the loop is dead.

It usually means the process is at the low end of the calibrated range.

Example:

4 mA = 0 PSI

But:

0 mA = open circuit, lost power, broken wire, failed transmitter, or disconnected loop

This is called a live zero signal.

A live zero helps the control system distinguish between a valid low reading and a failed signal.


Why the Signal Starts at 4 mA

The signal starts at 4 mA instead of 0 mA for two big reasons:

1. Fault Detection

If the PLC sees 0 mA, that is not a valid process reading. It usually means something is wrong.

Possible causes:

  • Broken wire
  • Open loop
  • Lost 24 VDC supply
  • Failed transmitter
  • Disconnected terminal
  • Blown fuse
  • Bad analog input circuit
2. Loop-Powered Transmitters

Many transmitters are 2-wire loop-powered transmitters.

This means the same two wires provide:

Power for the transmitter
AND
Signal back to the control system

In a 2-wire loop, the transmitter uses the loop current to operate while regulating that same current to represent the process measurement. The book explains that a loop-powered transmitter relies on a remote power source and acts like a current regulator in the series loop.


Basic 2-Wire Current Loop

A basic 2-wire 4–20 mA loop has:

24 VDC Power Supply
+ Transmitter
+ PLC Analog Input
+ Wiring

A simplified path looks like this:

+24 VDC → Transmitter → PLC Analog Input → 0 VDC/Common

The transmitter controls how much current flows in the loop.

Example:

Process ConditionLoop Current
Low end of range4 mA
Mid range12 mA
High end of range20 mA

The PLC analog input reads that current and converts it into a raw digital value. Then the PLC logic scales that raw value into engineering units.

4–20 mA → Raw Counts → Scaling → PSI, GPM, °F, %, Gallons

2-Wire vs 4-Wire Transmitters

Not every transmitter is wired the same way.

2-Wire Transmitter

A 2-wire transmitter uses the same two wires for power and signal.

Two wires = power + 4–20 mA signal

Common with:

  • Pressure transmitters
  • Level transmitters
  • Temperature transmitters
  • Flow transmitters
  • Smart HART transmitters

Advantages:

  • Less wiring
  • Common in process instrumentation
  • Easy to integrate with analog input cards
  • Works well over long cable runs

4-Wire Transmitter

A 4-wire transmitter usually has separate wires for power and signal.

Two wires = power
Two wires = signal

Common with:

  • Some flowmeters
  • Analyzers
  • Powered instruments
  • Devices with displays, heaters, or advanced electronics

The book notes that 4-wire transmitter systems require additional conductors, which means larger cables, more terminal blocks, and more installation cost compared with 2-wire loops.


Current Loop vs Voltage Signal

A 4–20 mA signal is a current signal, not a voltage signal.

That matters.

With current loops, the same current flows through all devices in the series loop.

This makes current loops useful in industrial environments because they are generally more tolerant of voltage drops across long wire runs than voltage-based signals like 0–10 VDC.

4–20 mA Current Signal

Good for:

  • Long cable distances
  • Industrial process instrumentation
  • Noise-prone environments
  • Fault detection with live zero
  • PLC analog inputs
0–10 VDC Voltage Signal

Common in:

  • Drives
  • HVAC controls
  • Shorter cable runs
  • Some machine controls
  • Smaller automation systems

Voltage signals can be affected more easily by voltage drop and electrical noise.


How the PLC Reads 4–20 mA

The PLC analog input card does not automatically know the process value.

It reads the electrical signal and converts it to a digital number.

Example:

4 mA  → Raw minimum
20 mA → Raw maximum

Then the PLC scales the raw value into engineering units.

Example:

Raw Analog Input → Scale Instruction → Tank_Level_Percent

For a level transmitter:

4 mA  = 0%
20 mA = 100%

For a pressure transmitter:

4 mA  = 0 PSI
20 mA = 100 PSI

For a temperature transmitter:

4 mA  = 32 °F
20 mA = 212 °F

The same 4–20 mA signal can represent many different things. The difference is the instrument range and the PLC scaling.


LRV and URV

Two common terms in instrumentation are:

TermMeaning
LRVLower Range Value
URVUpper Range Value

Example:

LRV = 0 PSI
URV = 100 PSI

That means:

4 mA  = LRV = 0 PSI
20 mA = URV = 100 PSI

Another example:

LRV = 32 °F
URV = 212 °F

That means:

4 mA  = 32 °F
20 mA = 212 °F

This is very important when troubleshooting HMI values.

If the transmitter range and PLC scaling do not match, the HMI value will be wrong even if the transmitter and wiring are good.


Example: Level Transmitter

Instrument:

LT-101
Range: 0–100%
Output: 4–20 mA
PLC Tag: AI_Tank_Level_Pct

Expected values:

Tank LevelCurrent
0%4 mA
25%8 mA
50%12 mA
75%16 mA
100%20 mA

PLC usage:

IF AI_Tank_Level_Pct < 15%
THEN Low_Level_Alarm = TRUE
IF AI_Tank_Level_Pct > 90%
THEN High_Level_Alarm = TRUE
IF AI_Tank_Level_Pct > 20%
THEN Pump_Start_Permissive = TRUE

This shows how a 4–20 mA signal becomes useful inside PLC logic.


Example: Pressure Transmitter

Instrument:

PT-201
Range: 0–150 PSI
Output: 4–20 mA
PLC Tag: AI_Discharge_Pressure_PSI

Expected values:

PressureCurrent
0 PSI4 mA
37.5 PSI8 mA
75 PSI12 mA
112.5 PSI16 mA
150 PSI20 mA

PLC usage:

IF AI_Discharge_Pressure_PSI > 125 PSI
THEN High_Pressure_Alarm = TRUE
IF AI_Discharge_Pressure_PSI > 140 PSI
THEN High_High_Pressure_Fault = TRUE

Measuring a 4–20 mA Signal

A technician may need to measure loop current when the HMI value does not match the field condition.

There are several ways to measure a 4–20 mA loop.

1. Standard Multimeter in Series

A normal multimeter can measure milliamps, but it must be connected in series with the loop.

That means the loop must be opened.

This can interrupt the process signal.

The book warns that breaking the loop can temporarily force the signal to 0 mA, which may affect the controller, trigger alarms, or upset the process. It recommends proper preparation before interrupting a live loop, such as notifying personnel, placing a controller in manual mode, or considering process alarms and shutdown functions.

2. Clamp-On Milliamp Meter

A clamp-on milliamp meter measures the signal without opening the circuit.

This is safer and faster when available.

The book explains that Hall-effect clamp-on milliammeters can measure small DC loop currents non-intrusively by clamping around the wire, avoiding the need to break the circuit.

3. Test Terminals

Some transmitters have dedicated TEST terminals.

These allow a technician to measure loop current without disconnecting the main loop wires.

The book explains that some process transmitters include test points specifically for measuring the 4–20 mA current signal without undoing wiring connections.

4. Shunt Resistor

A precision resistor can be placed in the loop. The technician measures voltage across the resistor and calculates current using Ohm’s Law.

V = I × R

The book explains that shunt resistors allow current measurement by measuring voltage across a known resistance, then applying Ohm’s Law.


Quick 4–20 mA Troubleshooting Table

Measured SignalPossible Meaning
0 mAOpen loop, no power, broken wire, failed transmitter
Less than 4 mAUnder-range, fault condition, wiring issue
4 mAValid 0% process value
12 mAValid 50% process value
20 mAValid 100% process value
Greater than 20 mAOver-range, fault condition, transmitter issue
Unstable mANoise, loose terminal, bad shield, failing transmitter
Correct mA but wrong HMI valueScaling or HMI tag issue

Professional Troubleshooting Method

When a 4–20 mA reading looks wrong, follow the signal path.

Step 1 — Verify the Process

Ask:

Is the real process condition actually what the HMI says?

Use:

  • Local gauge
  • Sight glass
  • Manual reading
  • Field display
  • Operator observation
  • Known process condition

Step 2 — Verify the Transmitter

Check:

  • Is the transmitter powered?
  • Is the display alive?
  • Is the range correct?
  • Is the process connection open?
  • Is an isolation valve closed?
  • Is the impulse line plugged?
  • Is the sensor damaged?
  • Is the transmitter in alarm mode?

Step 3 — Measure the Loop Signal

Check the actual mA value.

Example:

Measured loop current = 12 mA

For a 0–100 PSI transmitter:

12 mA should equal about 50 PSI

If the field pressure is 50 PSI and the signal is 12 mA, the transmitter is probably doing its job.


Step 4 — Verify the PLC Analog Input

Check:

  • Analog input LED/status
  • Raw input value
  • Channel configuration
  • Wiring polarity
  • Input common/reference
  • Card fault
  • Module diagnostics

Step 5 — Verify Scaling

Ask:

Does 4 mA equal the correct LRV?
Does 20 mA equal the correct URV?

Example problem:

Transmitter range: 0–150 PSI
PLC scaling: 0–100 PSI

Result:

HMI value will be wrong

PLC Logic Best Practices

For industrial PLC programs, separate analog handling into clear steps.

1. Raw Input
AI_PT201_Raw
2. Scaled Engineering Value
AI_PT201_Pressure_PSI
3. Signal Health
AI_PT201_Signal_OK
AI_PT201_UnderRange
AI_PT201_OverRange
4. Alarm Logic
PT201_High_Alarm
PT201_HighHigh_Fault
PT201_Low_Alarm
5. HMI Display
PT201_HMI_Display_PSI

This makes troubleshooting easier because the technician can see where the problem is.


Technician Example: HMI Shows 0 PSI

Problem:

HMI shows 0 PSI
Field gauge shows 50 PSI

Possible causes:

AreaPossible Problem
ProcessGauge may be wrong or isolated
TransmitterNo power, failed sensor, wrong range
LoopOpen wire, loose terminal, bad fuse
PLC InputBad channel, wrong configuration
ScalingWrong raw range or engineering range
HMIWrong tag or display format

Professional check:

  1. Verify actual pressure.
  2. Check transmitter display.
  3. Measure loop current.
  4. Confirm PLC raw input.
  5. Confirm scaling.
  6. Confirm HMI tag.

Key Takeaway

A 4–20 mA current loop is one of the most important links between field instrumentation and the PLC.

Remember:

4 mA  = 0% process value
12 mA = 50% process value
20 mA = 100% process value
0 mA = signal problem

The technician’s job is to follow the path:

Process → Transmitter → 4–20 mA Loop → PLC Analog Input → Scaling → HMI Display → Logic

If you understand this path, you can troubleshoot most analog instrumentation problems more professionally.


Final Thoughts

For automation technicians, 4–20 mA is not just a theory topic. It is a daily troubleshooting skill.

When a pressure, level, flow, or temperature value looks wrong on the HMI, do not guess. Measure the signal, verify the transmitter, check the PLC raw value, and confirm the scaling.

A strong technician understands that the PLC is only as good as the signal it receives.

Leave a Reply

Your email address will not be published. Required fields are marked *