10. Using the HIM: How to Navigate, View Parameters, and Troubleshoot a VFD


0

Introduction

The HIM, or Human Interface Module, is one of the most useful tools a technician can use when working with a Variable Frequency Drive.

A VFD can be controlled and diagnosed from different places: PLC, HMI, terminal block, communication network, software, or keypad. The HIM gives the technician direct access to the drive so they can view status, monitor output values, check fault codes, adjust speed locally, change parameters, and, on supported models, copy or transfer parameter sets.

A HIM is especially useful during:

Startup
Troubleshooting
Drive replacement
Parameter verification
Local testing
Fault review
Speed adjustment
Backup and restore
Maintenance work

The examples in this post use Allen-Bradley PowerFlex drives as a practical reference, but the same concept applies to most VFD brands. Some manufacturers call it a keypad, operator panel, control panel, display module, or drive operator interface.


1. What Is a HIM?

HIM stands for:

Human Interface Module

It is the operator/technician interface for the VFD.

Depending on the drive model, the HIM may be:

Built into the drive
Mounted remotely on the panel door
Handheld and connected with a cable
Removable from the drive
Used only for programming and troubleshooting

On Allen-Bradley PowerFlex drives, HIM options may include a fixed keypad, remote panel-mount display, or handheld module. PowerFlex documentation lists remote HIM options with LCD display, digital speed control, full numeric keypad on handheld versions, and CopyCat capability on supported modules.


2. Why the HIM Matters for Technicians

The HIM allows the technician to interact directly with the VFD without needing the PLC or HMI.

With a HIM, a technician may be able to:

View output frequency
View commanded frequency
View output current
View DC bus voltage
View drive status
View control source
View digital input status
View fault history
Acknowledge or clear faults
Edit parameters
Start/stop the drive locally, if enabled
Change speed locally, if enabled
Copy parameters, if supported

Most VFDs, and specifically PowerFlex 4, the condition or state of the drive is constantly monitored and changes are indicated on the integral keypad. It also notes that when a fault occurs, the keypad provides visual notification with a flashing fault code and flashing fault indicator.


3. HIM vs HMI

A common source of confusion is HIM vs HMI.

They sound similar, but they are not the same.

TermMeaningTypical LocationPurpose
HIMHuman Interface ModuleOn or near the VFDDirect drive programming and monitoring
HMIHuman-Machine InterfaceOperator panel or SCADA screenMachine/process operation

Simple explanation:

HIM = talks directly to the drive.
HMI = talks to the machine control system.

The HMI may show the operator a clean screen like:

Motor Running
VFD Faulted
Speed Setpoint
Output Frequency
Reset Fault

The HIM shows the technician direct drive information such as:

d001 Output Frequency
d003 Output Current
P036 Start Source
P038 Speed Reference
Fault Code

4. Local Control vs Remote Control

One of the most important things to understand when using a HIM is whether the drive is in local or remote control.

Local control usually means the drive is being controlled from the keypad/HIM.

Remote control usually means the drive is being controlled from:

Terminal block
PLC outputs
Analog input
Communication network
External controller

Local control means operation is done through the keypad on the front of the drive or a local control panel, where the operator or technician monitors and controls the drive through that keypad.


Technician Warning

Before pressing Start from the HIM, always verify:

[ ] Is it safe for the motor to run?
[ ] Is the machine clear?
[ ] Is the drive in Local or Remote?
[ ] Is the speed reference safe?
[ ] Is the direction correct?
[ ] Are safety interlocks active?
[ ] Is the process ready?

A HIM is powerful because it can sometimes bypass the normal operator interface. Use it carefully.


5. Common HIM Buttons

Every drive brand is different, but many HIM/keypad layouts include similar buttons.

Common buttons:

ButtonTypical Function
ESCBack out of menu / acknowledge fault display
SELSelect digit or parameter field
ENTERAccept selection or save value
UPIncrease value or scroll up
DOWNDecrease value or scroll down
STARTStart drive, if enabled
STOPStop drive
REVReverse direction, if enabled
RESETReset fault, if supported

Esc, Up/Down, Enter, and Sel to navigate parameter groups, view values, edit digits, cancel changes, or save changes.


6. Understanding Parameter Groups

VFD parameters are usually organized into groups.

For PowerFlex-style drives, common groups include:

d = Display Group
P = Basic Program Group
A = Advanced Program Group

The PowerFlex manual explains that parameter numbers and names are shown with a group letter, number, and parameter name, such as P031 [Motor NP Volts]. It also identifies groups such as Display, Basic Program, and Advanced Program.


Typical Parameter Group Purpose
GroupPurpose
Display GroupRead-only monitoring values
Basic Program GroupBasic motor and control setup
Advanced Program GroupI/O, communication, protection, advanced features

A technician should use the Display Group first when troubleshooting because it shows what the drive is actually seeing.


7. Viewing Parameters from the HIM

The exact steps depend on the drive model, but a basic flow looks like this:

1. Press ESC to enter or back into the parameter menu.
2. Use UP/DOWN to select the parameter group.
3. Press ENTER to select the group.
4. Use UP/DOWN to select the parameter number.
5. Press ENTER or SEL to view the value.
6. Press ESC to return without changing.

After power-up the drive displays a Display Group parameter, pressing Esc shows the parameter number, pressing Esc again allows group selection, Up/Down scrolls through groups, and Enter selects the group.


Good First Parameters to View

When troubleshooting, useful display values include:

Output Frequency
Commanded Frequency
Output Current
Output Voltage
DC Bus Voltage
Drive Status
Control Source
Digital Input Status
Fault Code

On a PowerFlex-style drive, examples may include:

d001 Output Frequency
d002 Commanded Frequency
d003 Output Current
d004 Output Voltage
d005 DC Bus Voltage
d006 Drive Status
d012 Control Source
d013 Control Input Status
d014 Digital Input Status

These values help you avoid guessing.


8. Editing Parameters from the HIM

Before editing any parameter, follow this rule:

Record the original value first.

Basic editing flow:

1. Navigate to the parameter.
2. Press ENTER or SEL to view/edit the value.
3. Use SEL to move between digits, if needed.
4. Use UP/DOWN to change the value.
5. Press ENTER to save.
6. Press ESC to cancel or back out.
7. Verify the new value.
8. Test operation safely.

Pressing Enter or Sel allows viewing or editing a parameter value, Sel can move digit to digit, Esc cancels a change and restores the previous value, and Enter saves the change.


Technician Note

Never change parameters randomly.

Before changing any value, ask:

[ ] What does this parameter control?
[ ] What is the current value?
[ ] What should the correct value be?
[ ] Is there a backup?
[ ] Is the machine safe to test after the change?
[ ] Does the change affect safety, speed, direction, braking, or restart behavior?

9. Viewing Faults from the HIM

When a VFD faults, the HIM/keypad usually displays a fault code or fault message.

A PowerFlex troubleshooting section explains that the integral keypad provides visual notification of a fault by displaying a flashing fault number and flashing fault indicator, and the technician can press Esc to regain control of the keypad.

Common fault information may include:

Fault code
Fault description
Fault history
Time of fault, if supported
Drive status at fault
Output current at fault, if supported
DC bus voltage at fault, if supported

Do Not Reset Blindly

A fault is information.

Before resetting, record:

[ ] Fault code
[ ] Fault description
[ ] Operating condition
[ ] Motor speed
[ ] Load condition
[ ] Whether it happened during start, run, or stop
[ ] Any recent parameter or wiring changes

Then troubleshoot the cause.


10. Common Faults You May See on a HIM

Common VFD faults include:

Fault TypeWhat to Think About
OvercurrentLoad, motor wiring, accel time, short circuit
OvervoltageDecel too fast, regeneration, high line voltage
UndervoltageLow input voltage, phase loss, power interruption
Motor OverloadMotor FLA setting, load, cooling, duty
Ground FaultMotor cable, motor winding, moisture
OvertemperatureFan, heatsink, cabinet cooling
Communication LossNetwork cable, adapter, node/IP settings
Analog Input LossSpeed signal, sensor, wiring, scaling

The PowerFlex troubleshooting material includes fault descriptions and corrective actions for faults such as Power Loss, UnderVoltage, OverVoltage, Motor Stalled, Motor Overload, Heatsink Overtemperature, Hardware OverCurrent, and Ground Fault.


11. Using HIM Display Values for Troubleshooting

The HIM is extremely useful because it can show what the drive is seeing in real time.

Example 1: PLC Says Run, But Drive Does Not Run

Check:

Control Source
Digital Input Status
Drive Status
Fault Code
Commanded Frequency

Possible findings:

Start Source is set to Keypad.
Terminal input is not active.
Stop input is missing.
Drive is faulted.
Speed reference is 0 Hz.

Example 2: Motor Runs at Wrong Speed

Check:

Commanded Frequency
Output Frequency
Speed Reference Source
Analog Input Value
Preset Speed Inputs
Control Source

Possible findings:

Drive is in Local mode.
Speed reference is Keypad.
Analog input is missing.
Preset speed is active.
Network reference is not being received.

Example 3: Drive Trips During Stop

Check:

Fault Code
DC Bus Voltage
Stop Mode
Decel Time
Dynamic Brake Settings
Output Frequency

Possible finding:

OverVoltage during deceleration because the load is regenerating energy back into the DC bus.

12. HIM CopyCat Function

Some HIM modules support a parameter copy function often called CopyCat.

CopyCat can allow the technician to:

Upload parameters from a drive to the HIM
Store the parameter set
Download parameters from the HIM to another compatible drive
Speed up replacement work
Reduce manual parameter entry errors

PowerFlex documentation lists both remote panel-mount and handheld HIM options as CopyCat capable. The handheld version also includes a full numeric keypad and cable, while the remote panel-mount version includes an LCD display and digital speed control.


CopyCat Use Case

A common field scenario:

Old VFD is still powering up.
Technician uploads parameter set into HIM.
Old drive is replaced.
Technician downloads parameter set into replacement drive.
Technician verifies motor data, I/O, communication, and direction.

This can save a lot of time.


CopyCat Warning

CopyCat is not magic.

Always verify:

[ ] Drive family compatibility
[ ] Firmware compatibility
[ ] Horsepower/current rating compatibility
[ ] Input voltage rating
[ ] Parameter structure
[ ] Communication settings
[ ] Motor nameplate data
[ ] Start source and speed reference
[ ] Digital input functions
[ ] Relay output functions
[ ] Direction of rotation

A copied configuration should always be verified before returning the machine to production.


13. HIM vs Software Backup

A HIM is great in the field, but software may provide better documentation.

Examples of software tools:

DriveTools SP
DriveExplorer
DriveExecutive
Connected Components Workbench
Manufacturer-specific software

PowerFlex documentation describes DriveTools SP as Windows-based software that provides a way to monitor or configure Allen-Bradley drives and communication adapters online and offline. It also describes DriveExplorer as software used to monitor or configure drives and adapters online/offline.


Comparison
MethodBest ForLimitation
HIMFast local access in the fieldSmall display, limited documentation
HIM CopyCatQuick replacement between compatible drivesCompatibility must be verified
DriveTools SP / DriveExplorerBackup, compare, print, online/offline workRequires PC, cable, software compatibility
Manual Parameter SheetUniversal methodTime-consuming, prone to errors
PLC-based parametersSome networked systemsNot always complete

14. Using the HIM During Drive Replacement

Before removing the old drive:

[ ] View and record fault history.
[ ] Record motor nameplate parameters.
[ ] Record Start Source.
[ ] Record Speed Reference.
[ ] Record Accel/Decel Times.
[ ] Record Stop Mode.
[ ] Record digital input functions.
[ ] Record relay output functions.
[ ] Record analog input settings.
[ ] Record communication settings.
[ ] Upload parameters using HIM CopyCat if supported.
[ ] Save software backup if possible.

After installing the replacement drive:

[ ] Download or enter parameters.
[ ] Verify motor data.
[ ] Verify start source.
[ ] Verify speed reference.
[ ] Verify I/O status.
[ ] Verify communication.
[ ] Test local mode safely.
[ ] Test remote/auto mode safely.
[ ] Verify motor rotation.
[ ] Verify feedback to PLC/HMI.
[ ] Save final backup.

15. Safety When Using the HIM

Using a HIM may seem simple, but the drive may be energized and capable of starting a motor.

Before using the HIM:

[ ] Know whether the drive is energized.
[ ] Follow required PPE rules.
[ ] Keep hands away from live terminals.
[ ] Understand local/remote mode.
[ ] Confirm the motor can safely run.
[ ] Do not change parameters without authorization.
[ ] Do not reset faults repeatedly without finding the cause.
[ ] Do not use local start if the machine is not clear.

The PowerFlex manual warns that only qualified personnel familiar with AC drives and associated machinery should plan, install, start up, or maintain the system. It also warns that the drive contains high-voltage capacitors that require time to discharge after power is removed.


16. Common HIM Mistakes

Avoid these mistakes:

[ ] Pressing Start locally without confirming machine status
[ ] Changing parameters without recording original values
[ ] Confusing output frequency with commanded frequency
[ ] Resetting faults without documenting the fault code
[ ] Leaving the drive in Local mode after troubleshooting
[ ] Assuming HIM speed is the same as PLC speed reference
[ ] Copying parameters to an incompatible replacement drive
[ ] Forgetting communication settings after replacement
[ ] Not verifying digital input status from the HIM
[ ] Not saving a final backup after changes

17. Practical Troubleshooting Flow Using the HIM

When the drive is not running:

1. Check fault code.
2. Check drive status.
3. Check control source.
4. Check digital input status.
5. Check commanded frequency.
6. Check output frequency.
7. Check output current.
8. Check speed reference source.
9. Check stop/enable input.
10. Verify local/remote mode.

When the drive is running but not correctly:

1. Check commanded frequency vs output frequency.
2. Check current.
3. Check DC bus voltage.
4. Check acceleration/deceleration settings.
5. Check speed reference source.
6. Check active preset speeds.
7. Check analog input signal.
8. Check fault/alarm history.

Simple Technician Explanation

A simple way to explain the HIM is:

The HIM is the technician’s direct window into the VFD.
It lets you see what the drive is doing, what it is commanded to do, and what fault or parameter may be stopping it from running correctly.

Or even shorter:

HIM = direct access to drive status, parameters, faults, and sometimes backups.

Final Thoughts

The HIM is one of the most practical tools for VFD troubleshooting.

A good technician uses the HIM to avoid guessing. Instead of only looking at the PLC or HMI, the technician checks what the drive itself is seeing:

Is the drive faulted?
What is the active control source?
Is the start input active?
Is the speed reference present?
What is the output frequency?
What is the output current?
What fault code occurred?
Are the parameters correct?

For VFD replacement, the HIM can also help with parameter transfer when CopyCat is supported. But even when using CopyCat, the technician must verify compatibility, motor data, I/O, communication, direction, and final operation.

A strong VFD troubleshooting mindset is:

Use the HIM to verify.
Use backups to protect the process.
Use the manual to confirm.
Use safe testing before returning to production.

Leave a Reply

Your email address will not be published. Required fields are marked *